BT/Power Equipment-Rectifier, Inverter and UPS/2022 Bhutan Telecom Ltd Contract Awarded


Procurement Category: Goods

Dzongkhag/Location: Thimphu

Goods/Services/Work Type: Retail Trade/Hardware/Electricals

Procurement Method: Open Tendering

Annual Procurement Plan: 2022

Bidding Process: Single Stage Bidding - Single Envelope

Contact Details: manager.powerandinfra@bt.bt/procurement@bt.bt

Status: Contract Awarded


Bidding Details

Submission Date: January 31 2023, 11:00 AM

Opening Date: January 31 2023, 02:00 PM

Prebid Date: None

Prebid Place: None

Earnest Money Deposit Details

EMD Type: Percent

EMD Value: 2.0%

Evaluation Details

Financial Evaluation: 100%

Agency Documents


Sl Document Link
1 Integrity Pact Document Download
2 RFP Download
Document Prerequisites For Participation


Sl Document
1 Catalogue/DataSheet
2 Integrity Pact Document
3 OEM Certificate
4 Other Document
5 Tax Clearance
6 Trade License
Tender Items(BOQ/BOM)


Sl Item Code Item Name,
Additional Description/Specifications
UoM Qty
1 FA00602 SMPS Rectifier Battery Charger, IP Vac = 180 – 280 Vac; OP = (-48V DC), 500 Amps, Modular Type with minimum 8 No of Modules and 8 slots of 60 Amps per module. Must have load facility to connect both critical and non critical loads using appropriate MCBs and HRC Fuse. Also should have an inbuilt controller having the following features to monitor the status of the rectifier, battery, room temperature, ac mains available or not, DG supply available or not, rectifier failure alarm, load on battery, load on AC or DG. All these parameters are to be monitored remotely using LAN/Modem, GSM, GPRS, Web browser. Remote alarming using dry contacts/SNMP. ( Vertiv/Delta / benning/Dynamic Power/Exicom), Set 22.0
2 FA00829 Solar-DG-Utility-Battery Hybrid MPPT system, modular type, 2 kW, 500 Amps, having min 6 (Five) solar mppt modules of 40 Amps capacity and 2 additional MPPT slots . 6 nos of rectifier module of capacity 80 amps and 2 additional rectifier slots having the following features: Must have load facility to connect both critical and non critical loads using appropriate MCBs and HRC Fuse. Further, the system also should have min two nos of appropriate rating of HRC fuses for connecting of min two battery banks of min 450 Ah per bank. Also should have an inbuilt controller having the following features to monitor the status of the rectifier, battery, room temperature, ac mains available or not, DG supply available or not, rectifier failure alarm, load on battery, load on AC or DG. All these parameters are to be monitored remotely using LAN/Modem, GSM, GPRS, Web browser. Remote alarming using dry contacts/SNMP: 1. Solar Converter Specs: Input voltage (DC), Vertiv/Delta/Eltek/Dynamic Power/Exicom, Set 27.0
3 FA00896 SMPS Rectifier Battery Charger, IP Vac = 3 phase, 4 Wire; OP = (-48V DC), 2500 Amps, Modular Type with minimum 30 No of Modules and 30 slots of 60/80 Amps per module. Must have load facility to connect both critical and non critical loads using appropriate MCBs and HRC Fuse. Also should have an inbuilt controller having the following features to monitor the status of the rectifier, battery, room temperature, ac mains available or not, DG supply available or not, rectifier failure alarm, load on battery, load on AC or DG. All these parameters are to be monitored remotely using LAN/Modem, GSM, GPRS, Web browser. Remote alarming using dry contacts/SNMP. Make: (Vertiv/Delta / benning/Dynamic Power), Set 1.0
4 FA00560 Rectifier Module R48-4000e, no 8
5 FA00559 Rectifier Module R48-3200, no 8
6 FA00561 Rectifier MPPT Modules S48-3000, no 12
7 FA00390 Inverter (3KVA), Rackmount, Input Voltage :44-55V DC, Output : 230V AC, nos 20.0
8 FA00391 Inverter ( 5KVA), Rackmount, Input Voltage: 44-55 VDC, OutPut:230V AC, no 12
9 FA00898 UPS: Double conversion on line UPS with external batteries 5kVA, 230 V AC Make: Delta/Vertiv/APC/Schneider , no 1