BT/Power Equipment-Batteries /2025 Bhutan Telecom Ltd Amendment Issued Participate
Procurement Category: Goods
Dzongkhag/Location: Thimphu
Goods/Services/Work Type: Retail Trade/Hardware/Electricals
Procurement Method: Open Tendering
Annual Procurement Plan: 2025
Bidding Process: Single Stage Bidding - Single Envelope
Contact Details: jigdrel.wangchuk@bt.bt/jiwan.kuikel@bt.bt/procurement@bt.bt
Status: Amendment Issued
Bidding Details
Submission Date: January 14 2025, 11:00 AM
Opening Date: January 14 2025, 02:00 PM
Prebid Date: None
Prebid Place: None
Earnest Money Deposit Details
EMD Type: Percent
EMD Value: 2.0%
Evaluation Details
Financial Evaluation: 100%
Agency Documents
Sl | Document | Link |
---|---|---|
1 | Integrity Pact Document | Download |
2 | RFP | Download |
Document Prerequisites For Participation
Sl | Document |
---|---|
1 | Catalogue/DataSheet |
2 | Integrity Pact Document |
3 | OEM Certificate |
4 | Tax Clearance |
5 | Trade License |
Tender Items(BOQ/BOM)
Sl | Item Code | Item Name, Additional Description/Specifications |
UoM | Qty |
---|---|---|---|---|
1 | FA01107 | Diesel Engine Generator Starting Batteries-SMF Lead Acid Battery, 12V, 100Ah, 550-1000CCA, | nos | 21.0 |
2 | FA01240 | Diesel Engine Generator Starting Batteries (Lead Acid Batteries) Voltage: 12V-130AH,SMF, 550-1000CCA, | nos | 5.0 |
3 | FA01241 | Diesel Engine Generator Starting Batteries (Lead Acid Batteries) Voltage: 12V-150AH,SMF , 550-1000CCA, | nos | 49.0 |
4 | FA01242 | SMPS Based Battery Charger, Input Voltage: 170 to 270 Vac, Output Voltage: 12 to 14 Vdc, | nos | 23.0 |
5 | FA01243 | UPS(3kVA, 230V), | nos | 1.0 |
6 | FA01063 | UPS Batteries – Sealed Maintenance Free, Valve Regulated Lead Acid Make: Amaron Quanta, Exide, HBL, equivalent 12V/200 Ah(Dimension 525mmX220mmX225mm) , | nos | 184.0 |
7 | FA01252 | SMF VRLA-2v/1530 Ah @C10 @1.75 ECV @27 Deg.C (+) 48V DC, 4590, Ah* 4 banks ( 288 cells)= 4590 Ah. Dimension(20cmX52cmX11.25cm), | nos | 288.0 |
8 | FA01249 |
Automatic Voltage Regulators - 20KVA 1 phase, Input: 150/250V
1.Technical Specifications:
Servo controlled voltage stabilizer
-Rating: 20 kVA, 1 phase
-Input Voltage Range: 150 – 280 V ac
-Output Voltage: 230V +/- 1%
-Correction of speed: 8V to 70V per sec.
-Correction method: Step-less Auto Variable Transformer/Roller contact type
- Cooling: Natural Air Cooled
-Efficiency: 97% – 99%
-Type & Suitability: Unbalance supply and unbalance load, suitable for all power factor loads.
-No load loss: less than 0.4%
-Overload capability: up to 150% momentarily.
-Duty cycle: Continuous 24X7
-Response time: less than 10ms
2. Optional features and protections:
-Overload and short circuit protection
-Low/High voltage cut off
-Single phase prevention/reverse phase prevention
-Stabiliser bypass system
-Earth fault protection
-Spike and surge protection
-Digital/Anolog meters to show voltage and current
-Option to operate in both auto and manual mode
,
Automatic Voltage Regulators - 20KVA 1 phase, Input: 150/250V |
nos | 2.0 |
9 | FA01250 | AMF Panel, 20kVA 1 ph. -The AMF Panels which can interface with DG-Grid-Battery. Automatic mains failure (AMF) panel should automatically switch to DG in the event of loss or failure of commercial power or with 48V DC system. Further, the AMF panel also should have both Mains and DG contactors having wide range of coil operating on DC voltage (40 – 60V DC) and should have the DC battery charger(I/P-40-60v DC, O/P-13v DC 20 Amps) to charge the starting battery of DG., | nos | 4.0 |
10 | FA01251 | Fire Extinguisher (ABC Type, 9Kg) , | nos | 66.0 |
Amendment Details
Sl | ID | Date | Details | Remarks |
---|---|---|---|---|
1 | TAM24120005 | December 13 2024, 03:42 PM | Notification changed from None to None | Specification changed for S/n-9 Previous Technical Specification: AMF Panel, 20kVA 1 ph. -The AMF Panels which can interface with DG-Grid-Battery. Automatic mains failure (AMF) panel should automatically switch to DG in the event of loss or failure of commercial power or with 48V DC system. Further, the AMF panel also should have both Mains and DG contactors having wide range of coil operating on DC voltage (40 – 60V DC) and should have the DC battery charger(I/P-40-60v DC, O/P-13v DC 20 Amps) to charge the starting battery of DG. Amended Specification- "AMF Panel, 20kVA 1 ph.Technical specifications: a)Master switch: Control On/Off b)Event Log c)Remote two-wire start/stop capability d)One-source responsibility for generating system & accessories e)Automatic start with programmed cranking cycle f)Field software upgrade possibility g)Operating temperature: -20°C to 70°C (-4°F to 158°F) h)Storage temperature: -20°C to 70°C (-4°F to 158°F) i)Humidity: 0-95% condensing j)Control Panel k)Alternator to control panel connection with copper cable only MCCB/MCB details: with short circuit and overload protection. Output copper cable size (Sq. mm): 1 run/ph. Microprocessor based AMF control panel capable of extending Remote monitoring system GPRS/EDGE/WCDMA/LTE based generator for remote monitoring system." |
2 | TAM24120018 | December 24 2024, 04:10 PM | Notification changed from None to None | Specification change for item-FA01252 Previous - SMF VRLA-2v/1530 Ah @C10 @1.75 ECV @27 Deg.C (+) 48V DC, 4590, Ah* 4 banks ( 288 cells)= 4590 Ah. Dimension(20cmX52cmX11.25cm) Amended- SMF VRLA-2V/CELL, 4590 Ah @C10 @1.75 ECV @27 Deg.C (+) 48V DC, 13770 Ah* 4 banks ( 288 cells)= 13770 Ah - Dimension(20cmX52cmX11.25cm) |